PERIODIC TEST TABLE
|
Type Of Installation |
Routine Check sub-clause 2.1.4 |
Maximum peroid
between inspections & testing as necessary |
|
General Installations |
. |
. |
|
Domestic |
------- |
Change of tenancy/10 years |
|
Commercial |
1 Year |
Change of tenancy/5 years |
|
Educational Establishments |
4 months |
5 Years |
|
Hospitals |
1 Year |
5 Years |
|
Industrial |
1 Year |
3 Years |
|
Residential Accommodation |
At change of occupancy/1 Year |
5 Years |
|
Offices |
1 Year |
5 Years |
|
Shops |
1 Year |
5 Years |
|
Laboratories |
1 Year |
5 Years |
|
. |
. |
. |
|
Buildings Open To The Public |
. |
. |
|
Cinemas |
4 Months |
1 Year |
|
Church Installations |
1 Year |
5 Years |
|
Leisure Complexes |
4 Months |
1 Year |
|
Places of Public Entertainment |
4 Months |
1 Year |
|
Restaurants & Hotels |
1 Year |
5 Years |
|
Theatres |
4 Months |
1 Years |
|
Public Houses |
1 Year |
5 Years |
|
Village Halls/Community Centres |
1 Year |
5 Years |
|
. |
. |
. |
|
External Installations |
. |
. |
|
Agricultural & Horicultural |
1 Year |
3 Years |
|
Caravans |
1 Year |
3 Years |
|
Caravan Parks |
6 Months |
1 Year |
|
Highway Power Supplies |
As Convenient |
6 Years |
|
Marinas |
4 Months |
1 Year |
|
Fish Farms |
4 Months |
1 Year |
|
. |
. |
. |
|
Special Installations |
. |
. |
|
Emergency Lighting |
Daily/ Monthly |
3 Years |
|
Fire Alarms |
Daily/ Monthly/Weekly |
1 Year |
|
Launderettes |
1 Year |
1 Year |
|
Petrol Filling Stations |
1 Year |
1 Year |
|
Construction Site Installations |
3 Months |
3 Months |
*Recommendations taken from BS7671